Feedback
AhlsellProductsElectricPanels and fuses 20-2421 Standard componentsResidual Current DeviceEarth fault breakers
Garo
Ground fault circuit interrupter type RCCB GS, 2 and 4-pole, 10kA
RCCB GS 25A 2P 30MA RCCB GS 25A 30MA 10KA 2P
Article number: Suppl. article no:
2163321
110092
to see price and stock
Earth fault circuit breakers 10kA are adapted for installation in protecting persons and equipment for fault currents at short-circuit currents up to 10kA. On all GARO earth-fault circuit breakers, voltage supply can be performed on the upper or lower side and on all 2-pole earth-fault circuit breakers it is possible to connect neutral conductors on the right or left side. All earth fault circuit breakers are tested and approved by independent European test institutes.
- Article number: 2163321
- Suppl. article no: 110092
- Ean no: 7331185209968
- Material class QL4001
Technical data
- Packagin Size: 1 ST/51 ST
- Leakage current type: A
- Number of poles: 2
- Rated voltage: 230 V
- Rated current: 25 A
- Rated fault current: 30 mA
- Built-in depth: 68 mm
- Width in number of modular spacings: 2
- Surge current capacity: 0 kA
- Selective protection: No
- Short-circuit breaking capacity (Icw): 10 kA
- Frequency: 50/60 Hz
- Short-time delayed tripping: No
- Degree of protection (IP): IP20
- Additional equipment possible: Yes
- Connectable conductor cross section solid-core: 1-25 mm²
- Connectable conductor cross section multi-wired: 1-25 mm²
- Mounting method: DIN rail
- Pollution degree: 2
- Rated impulse withstand voltage Uimp: 4 kV
- Rated insulation voltage Ui: 440 V
- Ambient temperature during operating: 25-55 °C
- With interlocking device: No
- REACH Date: 2021-06-15
- REACH Information obligation: No