Feedback
AhlsellProductsElectricAutomation 29-4538 Sensors, machine safetySurveillance relays, pressure guardsLevel monitoring

Carlo Gavazzi
Level control relay type CLP2F
COND.LEVEL 2+1 MULTIPLEX PLUG CLP2FA1B230
Article number: Suppl. article no:
3864382
CLP2FA1B230
to see price and stock
Relay for level control of conductive liquids, 11-pins socket connection - broader sensitivity!
The relay is used for regulation of conductive liquids where the level must be between a minimum and maximum value or where a level may not be above or below a maximum. When filling, Fill is selected (left scale] on the lower dial and when emptying, Empty (right scale) is selected. If only one level is desired, for example overfilling or dry running protection, use E38 644 20 and connect the electrodes on plinth 5-7 and bridge 5-6 and 7-11 (master). 7-11 shall always be breached for a system! With a cascade connection/indication of several levels (max 7 relays), refer to the products Swedish datasheet. All relevant data and the circuit diagram are clearly marked next to the relays.
Technical data:
Relay output 1alternating contact, AC1 8 A / 250 VAC (2500 VA)
Sensor voltage max 5 VAC, 2 mA
Sensor sensitivity Mode L (low sensitivity) 250-5kohm, Mode S (standard sensitivity) 50k-500kohm, fine adjustment of the upper potentiometer (the factory setting works in most cases, that is, Mode S and max on the upper potentiometer).
Reaction time approx. 1s
Operating temperature -20º to +50º C
Indication 2 LED, green light when the control voltage is connected, yellow light when the relay is closed.
Dimensions (mm) 36x81x60
The relay is used for regulation of conductive liquids where the level must be between a minimum and maximum value or where a level may not be above or below a maximum. When filling, Fill is selected (left scale] on the lower dial and when emptying, Empty (right scale) is selected. If only one level is desired, for example overfilling or dry running protection, use E38 644 20 and connect the electrodes on plinth 5-7 and bridge 5-6 and 7-11 (master). 7-11 shall always be breached for a system! With a cascade connection/indication of several levels (max 7 relays), refer to the products Swedish datasheet. All relevant data and the circuit diagram are clearly marked next to the relays.
Technical data:
Relay output 1alternating contact, AC1 8 A / 250 VAC (2500 VA)
Sensor voltage max 5 VAC, 2 mA
Sensor sensitivity Mode L (low sensitivity) 250-5kohm, Mode S (standard sensitivity) 50k-500kohm, fine adjustment of the upper potentiometer (the factory setting works in most cases, that is, Mode S and max on the upper potentiometer).
Reaction time approx. 1s
Operating temperature -20º to +50º C
Indication 2 LED, green light when the control voltage is connected, yellow light when the relay is closed.
Dimensions (mm) 36x81x60
- Article number: 3864382
- Suppl. article no: CLP2FA1B230
- Ean no: 5709870381404
- Replaces art.nbr: 3864357
- Material class QP029B
Technical data
- Type: CLP2FA1B230
- Design: 11-pole
- Type of electric connection: Screw connection
- Rated control supply voltage DC: 0 V
- Voltage type for actuating: AC
- With detachable clamps: No
- Number of inputs for electrodes: 3
- Min. adjustable operate delay time: 1.3 s
- Max. permitted operate delay time: 1.3 s
- Min. adjustable off-delay time: 1 s
- Max. permitted off-delay time: 1 s
- Response value sensitivity adjustable: Yes
- Number of contacts as normally closed contact: 0
- Number of contacts as normally open contact: 0
- Number of contacts as change-over contact: 1
- Physical measurement principle: Conductive
- Width: 35.5 mm
- Height: 81 mm
- Depth: 60.2 mm
- Rated control supply voltage AC 60 Hz: 195-265 V
- Rated control supply voltage AC 50 Hz: 195-265 V