20 Fuse material

Do you need fuses? Ahlsell helps you find installation material for all your electrical jobs. Whether you work with commercial properties or private residences, we have the range for your next project. We offer products from several well-known suppliers. Here you will find wall sockets, cable ladders, and accessories for easy installations. We also offer smart wall sockets, switches, and dimmers from several major suppliers. Modern products for modern solutions. All the installation material you need under one roof. A job well done begins with good materials. Explore our wide range of fuses, installation materials, and accessories here in the online store or visit your nearest Ahlsell shop.

Bygg din elcentral och strömställare med drag and drop-funktion med Schneider Electric eDesign
Melt metals TG N
Gevea
Melt metals TG N
Art. no.: 2056606
For separator fuses L33 equipped with ejector springs. Melting metal TG consists of a melting wire housed in a water resistant piping material, which is highly gas-emitting when it is exposed to the breaker light arc. The melting metal is equipped with soft litz connections for the ejector springs. It has the same dimension regardless of the voltage.
TG has low spreading around the average curve. The selectivity can always be calculated between two adjacent fuse sizes when these are used as short-circuit protection.
If the fuse is used as overload protection, the larger fuse should have a rated current of at least 1.5 times the smaller.
Protected transformers highest rated current A should not exceed the melting metal’s rated current.
High-power fuse “Swedish design" 12kV
Ifö Electric
High-power fuse “Swedish design" 12kV
Art. no.: 2059146
Sub-field fuses - Back-up fuses are designed for short disconnection times in the event of arc failure on the low voltage side of the distribution transformers.
The fuses are intended as current limiting / short-circuit protection, which will trigger all currents between its maximum breaking current Imax (I1) down to the Imin (I3) value.
The fuses correspond to the requirements of the older Swedish test standard 17A- "Swedish fusing" through:

• The switch-off time is adapted to the rated current of the fuse (safe disconnection at 0.1s)
• The rated current of the fuse corresponds to the requirements of being greater than 1.1 times the rated current of the transformer.
• The fuses meet the requirements for the connection currents according to 17A.

The fuses are also dimensioned to allow the transformers to run with 40% overload for 2 hours. The fuses are tested and approved in accordance with current test standard IEC 60282-1 and VDE 0670 T4.
Dimensionally, the fuses meet DIN 43625 and are designed for use both indoors and outdoors. The low effect losses in the fuses make them suitable for use in encased switchgear. In these applications where cooling is reduced, the effect loss of the fuse should be considered when selecting rated current of the fuse. The fuses are lead- and cadmium free and equipped with striking pin, type medium 80 N (Newton). The entire range extends to 12 kV from 6A-160A and for 24 kV from 4A-125A. the fuses have clear marking with technical data and E-number to avoid mistakes as well as reinforced marking around the entire fuse body of the striking pin position. This marking simplifies post-checking of the mounting direction to ensure the function of the striking pin. The striking pin is activated either by melted melting conductors or via built-in temperature sensors.
Showing 52 of 68