Feedback
Hager
Main switch 125A HAD
MAINBREAKER 125 A, 3-POLIG
Artikelnummer: Lev. artikelnr:
2108677
HAD312
för att se saldo och pris
Main circuit breaker in module version can be mounted in all standard casings and cabinets. Load-break switch with independent hand operation and visible switch point. The switches are mounted on DIN rail.
- Article number: 2108677
- Suppl. article no: HAD312
- Ean no: 3250613140441
- Material class QL240A
Teknisk data
- Packagin Size: 1 ST/12 ST/288 ST
- Type: HAD312
- Number of poles: 3
- Width in number of modular spacings: 5
- Rated permanent current Iu: 125 A
- Rated operation power at AC-23, 400 V: 56 kW
- Version as main switch: Yes
- Version as safety switch: Yes
- Type of control element: Short thumb-grip
- Version as maintenance-/service switch: Yes
- Device construction: Built-in device fixed built-in technique
- Type of electrical connection of main circuit: Screw connection
- Interlockable: Yes
- Suitable for front mounting 4-hole: No
- Suitable for front mounting centre: No
- Suitable for floor mounting: Yes
- Suitable for distribution board installation: Yes
- Suitable for intermediate mounting: No
- Max. rated operation voltage Ue AC: 415 V
- Motor drive optional: No
- Degree of protection (IP), front side: IP20
- Voltage release optional: No
- Number of auxiliary contacts as normally open contact: 0
- Number of auxiliary contacts as change-over contact: 0
- Number of auxiliary contacts as normally closed contact: 0
- Version as emergency stop installation: No
- Conditioned rated short-circuit current Iq: 25 kA
- Motor drive integrated: No
- Colour control element: Grey
- Rated short-time withstand current lcw: 2.75 kA
- Rated permanent current at AC-21, 400 V: 125 A
- Rated permanent current at AC-23, 400 V: 100 A
- Rated operating voltage: 380-415 V
- Switching power at 400 V: 82 kW
- Degree of protection (NEMA): Other
- Version as reversing switch: No
- Number of switches: 1
- REACH Date: 2021-06-16
- REACH Information obligation: No