Feedback
AhlsellProductsElectricInstallation equipment 11-1813 Motion, time, light controlPresence detectorsPresence detectors Dali
Niko-Servodan
Motion sensor, 360° 41-761 High Ceiling
PRESENCE SENSOR SF DALIM HI CE MASTER
Article number: Suppl. article no:
1300244
41-761
to see price and stock
The motion sensor 41-761 Master is intended for ceiling mounting. Detection area can be broadened with slave sensor 41-762 and/or 41-763.
The sensor has 4 separate zones, of which 2 or 3 zones are daylight controlled and 1 or 2 zones intended for separate control with on/off or dimming, depending on the type of light fixtures.
The sensor is equipped with DALI output for controlling light zones and potential-free relay output for controlling either lighting, HVAC or as cut-off of voltage to DALI luminaries.
Settings
Using the remote control, one can choose between various functions for connecting control buttons, persistence time and lux settings.
Options
All functions provide the ability for auto on/offf or active on/off with auto off. Daylight control in up to 3 zones and relay output for HVAC
Daylight control in up to 3 zones and relay output for lighting on/off. Daylight control in up to 3 zones and relay output for cut-off (Stand-by minimization)
Daylight control in up to 3 zones for corridor solutions with day/night function and relay output for HVAC.
Programming during installation uses remote control 41-934.
The sensor has 4 separate zones, of which 2 or 3 zones are daylight controlled and 1 or 2 zones intended for separate control with on/off or dimming, depending on the type of light fixtures.
The sensor is equipped with DALI output for controlling light zones and potential-free relay output for controlling either lighting, HVAC or as cut-off of voltage to DALI luminaries.
Settings
Using the remote control, one can choose between various functions for connecting control buttons, persistence time and lux settings.
Options
All functions provide the ability for auto on/offf or active on/off with auto off. Daylight control in up to 3 zones and relay output for HVAC
Daylight control in up to 3 zones and relay output for lighting on/off. Daylight control in up to 3 zones and relay output for cut-off (Stand-by minimization)
Daylight control in up to 3 zones for corridor solutions with day/night function and relay output for HVAC.
Programming during installation uses remote control 41-934.
- Article number: 1300244
- Suppl. article no: 41-761
- Ean no: 5703102208972
- Material class QI260A
Technical data
- Product series: 41-700
- Model: Presence detector
- Diameter reach on floor: 32 m
- Max. reach frontally: 32 m
- Max. reach sideways: 32 m
- Colour: White
- With DALI interface: Yes
- HVAC-control: Yes
- Mounting method: Surface mounted
- Detection angle horizontal: 0-360 °
- Max. duty cycle: 1000 min
- Degree of protection (IP): IP54
- Response value luminosity: 100-2000 lx
- Max. switching power: 2300 W
- Max. starting current: 800 A
- Material quality: Thermoplastic
- Response value luminosity adjustable: Yes
- Min. switch-on time: 300 s
- Voltage type: AC
- Frequency: 50 Hz
- With alarm function: No
- Dim function with dimmer basic element: Yes
- Animal zone: No
- Remote operation: Yes
- Forced switch off: Yes
- Networkable: No
- Bridging switch: No
- Material: Plastic
- Halogen free: Yes
- Constant light control: Yes
- Suitable for wireless transmission: No
- With signal unit: Yes
- Substation input: No
- Optimum mounting height: 8 m
- RAL-number (similar): 9010
- Response value sensitivity adjustable: Yes
- Teach-function for response value luminosity: No
- Temperature: -5-50 °C
- Transparent: No
- Staircase light controller: No
- Surface finishing: Matt
- Creep-under protection: No
- Surface protection: Other
- Nominal voltage: 230 V
- Switch-off delay: 3600 s
- Suitable for C-load: Yes
- With remote control: No
- Height: 64.1 mm
- Diameter: 117.3 mm
- REACH Date: 2022-01-17
- REACH Information obligation: No