Feedback

Rutab

Control and machine cable PVC NOVOFLEX NCY, EMC, Rutab

NOVOFLEX NCY4G2.5 (*0)
Article number: 
0282920





 to see price and stock
Flexible oil-resistant cable with good resistance to impact of chemicals, acids and lyes. The fine-wired structure in combination with the PVC jacket provides an elastic cable with a small bend radius. The cable is equipped with a screen of tinned braided copper wire, which protects against mechanical stress and, above all, shields against electric shocks, both inside and outside the cable (EMC Directive). The cable is used as control and operating cable on and in industrial machinery, in refrigeration and ventilation installations, in data and signal systems. Can be used in dry and wet environments. For installing between frequency converter and motor cable NCY 3-Plus is recommended.

Approval: Complies with Swedish and European standards in accordance with SS EN 60204
Operating voltage: 300/500 V
Line construction: Fine-wired blank copper.
Line insulation: PVC, black with white numbering.
Protective line: Green/Yellow
Inner jacket: PVC
Screen: Braid made of tinned copper
Outer jacket: PVC. Colour Transparent
Fixed wiring: 4 x cable diameter
Movable wiring: 15 x cable diameter
Temperature range Fixed wiring: -40°C - +70°C
Temperature range Movable wiring: -5°C - +70°C
Fire class: IEC 60 332-1 (F2)
  • Article number: 
    0282920
  • Material class 
    QA4200
  • This is an alternative to item  
    0278110
Technical data
  • Cable type: NOVOFLEX NCY
  • Dimension conductor x area: 4G2,5 mm²
  • Outer diameter approx.: 11.3 mm
  • Number of cores: 4
  • Nominal cross section conductor: 2.5 mm²
  • Colour outer sheath: Colourless
  • Weight: 233 kg/km
  • With protective conductor: Yes
  • Material core insulation: Polyvinyl chloride (PVC)
  • Nominal voltage U0: 300 V
  • Nominal voltage U: 500 V
  • Screen over stranding: Braiding
  • Conductor category: Class 5 = flexible
  • Material outer sheath: Polyvinyl chloride (PVC)
  • Core identification: Numbers
  • Permitted cable outer temperature during assembling/handling: -15-70 °C
  • Permitted cable outer temperature after assembling without vibration: -40-80 °C
  • Shape of conductor: Round
  • Min. permitted bending radius, moving application/free movement: 169.5 mm
  • Min. permitted bending radius, stationary application/permanent installation: 67.8 mm
  • Cable geometry: Round
  • Conductor resistance at 20 °C: 7.98 Ohm/km
  • Max. permitted conductor temperature: 70 °C
  • Screen: Yes
  • REACH Date: 2021-11-24
  • REACH Information obligation: No