Feedback
AhlsellProductsElectricCable 00-05, 48-4901 Control cable, single core and strandedControl cable halogen-free

Nexans
Control cable FQFR 450/700V Dca, Nexans
FQFR 7X1.5 500V LGREY 750 K
Article number: Suppl. article no:
0127790
16490198-898-00
to see price and stock


The cable is intended for fixed installation indoors and outdoors, even in ground and water, for control, measuring and signaling functions in power engineering plants.
FQFR is a halogen-free, PEX-insulated, copper-wire shielded and HFFR-coated control cable with round copper wire conductors. The cable is designed according to SS 424 03 21 in applicable parts. The conductors have thread count and resistance according to IEC 60228 class 2. The parties are number marked according to SS 424 17 20. The jacket is marked Manufacturer + Type / year + month / meter marking. FQFR meets fire spread class D. The cable is approved by SEMKO.
The cable is marked with Lifemark TM recycling mark (content declared).
FQFR is a halogen-free, PEX-insulated, copper-wire shielded and HFFR-coated control cable with round copper wire conductors. The cable is designed according to SS 424 03 21 in applicable parts. The conductors have thread count and resistance according to IEC 60228 class 2. The parties are number marked according to SS 424 17 20. The jacket is marked Manufacturer + Type / year + month / meter marking. FQFR meets fire spread class D. The cable is approved by SEMKO.
The cable is marked with Lifemark TM recycling mark (content declared).
- Article number: 0127790
- Suppl. article no: 16490198-898-00
- Ean no: 7330000076273
- Replaces art.nbr: 0158120
- Material class QA300A
Technical data
- Cable type: FQFR
- Dimension conductor x area: 7x1,5 mm²
- Number of cores: 7
- Nominal cross section conductor: 1.5 mm²
- With protective conductor: Yes
- Outer diameter approximate: 14 mm
- Weight/100 m: 29 kg
- Weight: 293 kg/km
- Reaction-to-fire according to EN 13501-6: Class: Dca
- Reaction-to-fire according to EN 13501-6: Flaming droplets/particles: d2
- Shape of conductor: Round
- Conductor material: Copper
- Conductor surface: Bare
- Conductor category: Class 2 = stranded
- Colour outer sheath: Grey
- Permitted cable outer temperature after assembling without vibration: -40-70 °C
- Permitted cable outer temperature during assembling/handling: -10-50 °C
- Material outer sheath: Polyolefin
- Material core insulation: Polyolefin
- Low temperature resistant according to EN 60811-504+505+506: Yes
- Nominal voltage U: 750 V
- Nominal voltage U0: 450 V
- Core identification: Numbers
- Reaction-to-fire according to EN 13501-6: Smoke production: s2
- Reaction-to-fire according to EN 13501-6: Acidity: a2
- Min. permitted bending radius, stationary application/permanent installation: 112 mm
- Cable geometry: Round
- Conductor resistance at 20 °C: 12.1 Ohm/km
- Core identification according to HD 308 S2: Yes
- Drain wire: No
- Max. permitted conductor temperature: 70 °C
- Screen: Yes
- Halogen free according to EN IEC 60754-2: Yes
- REACH Date: 2021-06-14
- With rodent protection: No
- Core colour: White
- REACH Information obligation: No
- Halogen free according to EN 60754-1/2: Yes
- Suitable for underground installation: Yes
- Radial water blocking cable: No