Feedback

Ground cable AXQ Infra 1kV Dca, Nexans - AXQ INFRA 4G50 1kV BLACK
Nexans

Ground cable AXQ Infra 1kV Dca, Nexans

AXQ INFRA 4G50 1kV BLACK
Article number: 
0009410
Suppl. article no: 
15236898-201-00





 to see price and stock
AXQ INFRA is a halogen-free, PEX-insulated and HFFR-sheathed cable with sector-shaped (50-240 mm²) or round (16-25 mm²) thin aluminum conductors. The cable for TNS systems has a ground conductor of annealed copper (50-240 mmm²). 16-25 mm² and 50-240 for TNC systems have ground conductors and aluminum PEN conductors.
  • Article number: 
    0009410
  • Suppl. article no: 
    15236898-201-00
  • Ean no: 
    7330000191761
  • Material class 
    QA1300
  • This is an alternative to item  
    0013790
Technical data
  • Packagin Size: 1 M/500 M
  • Cable type: AXQ INFRA
  • Nominal cross section conductor: 50 mm²
  • Number of cores: 4
  • Dimension conductor x area: 4G50 mm²
  • Outer diameter approximate: 27 mm
  • Colour outer sheath: Black
  • Weight: 846 kg/km
  • With protective conductor: Yes
  • Conductor material: Aluminium
  • Number of pilot/reduced conductors: 0
  • Core identification: Colour
  • Conductor category: Class 2 = stranded
  • Nominal voltage U: 1 kV
  • Nominal voltage U0: 0.6 kV
  • Max. permitted conductor temperature: 90 °C
  • Drain wire: No
  • Screen: No
  • Lead sheath: No
  • Reaction-to-fire according to EN 13501-6: Class: Dca
  • Reaction-to-fire according to EN 13501-6: Flaming droplets/particles: d2
  • Reaction-to-fire according to EN 13501-6: Smoke production: s2
  • Reaction-to-fire according to EN 13501-6: Acidity: a2
  • Fibre optic elements: No
  • Halogen free according to EN IEC 60754-2: Yes
  • Inner semi-conducting layer: No
  • Concentric conductor: None
  • Laminated sheath: No
  • Conductive coating: No
  • Shape of conductor: Sector-shaped
  • Conductor surface: Bare
  • Longitudinal water blocking conductors: No
  • Material outer sheath: Polyolefin
  • Permitted cable outer temperature after assembling without vibration: -40-70 °C
  • Permitted cable outer temperature during assembling/handling: -10-50 °C
  • Outer semi-conducting layer: No
  • Min. permitted bending radius, stationary application/permanent installation: 216 mm
  • Specification core insulation: Crosslinked polyethylene (XLPE)
  • Certified for shipboard application: No
  • Certified as airport lighting cable: No
  • Cable geometry: Round
  • Conductor resistance at 20 °C: 0.641 Ohm/km
  • Suitable for underground installation: Yes
  • Max. tensile strength during installation: 6 kN
  • With rodent protection: No
  • UV resistant: Yes
  • REACH Date: 2023-10-12
  • REACH Information obligation: No