Feedback

Nexans

Ground cable FXQJ Easy EMC Dca, Nexans

FXQJ EMC 3X70/35 1kV BL T500
Article number: 
0009185
Suppl. article no: 
15182498-201-05





 to see price and stock
FXQJ is a halogen-free, PEX-insulated and HFFR-sheathed cable with few-wire sector-shaped copper conductors. The cable has a screen of annealed copper wire with a full-covering anti-helix.
  • Article number: 
    0009185
  • Suppl. article no: 
    15182498-201-05
  • Material class 
    QA0450
Technical data
  • Packagin Size: 500 M
  • Cable type: FXQJ Easy
  • Number of cores: 4
  • Nominal cross section conductor: 70 mm²
  • Dimension conductor x area: 3x70/35 mm²
  • Outer diameter approx.: 31 mm
  • Colour outer sheath: Black
  • Weight: 2557 kg/km
  • Nominal voltage U: 1 kV
  • Nominal voltage U0: 0.6 kV
  • Halogen free according to EN IEC 60754-2: Yes
  • Reaction-to-fire according to EN 13501-6: Class: Dca
  • Reaction-to-fire according to EN 13501-6: Smoke production: s2
  • Reaction-to-fire according to EN 13501-6: Flaming droplets/particles: d2
  • Reaction-to-fire according to EN 13501-6: Acidity: a2
  • Conductor material: Copper
  • Conductor category: Class 2 = stranded
  • Shape of conductor: Sector-shaped
  • Screen: Yes
  • Drain wire: No
  • Lead sheath: No
  • Permitted cable outer temperature after assembling without vibration: -40-70 °C
  • Permitted cable outer temperature during assembling/handling: -10-50 °C
  • Concentric conductor: Copper
  • Material outer sheath: Polyolefin
  • Nominal cross section concentric conductor: 35 mm²
  • Core identification: Colour
  • With protective conductor: Yes
  • Material core insulation: Other
  • Max. conductor temperature: 90 °C
  • Fibre optic elements: No
  • Inner semi-conducting layer: No
  • Laminated sheath: No
  • Conductive coating: No
  • Conductor surface: Bare
  • Longitudinal water blocking screen: No
  • Longitudinal water blocking conductors: No
  • Low smoke according to EN IEC 61034-2: Yes
  • Outer semi-conducting layer: No
  • Certified for shipboard application: No
  • Certified as airport lighting cable: No
  • Cable geometry: Round
  • Min. permitted bending radius, stationary application/permanent installation: 248 mm
  • Core identification according to HD 308 S2: Yes
  • Conductor resistance at 20 °C: 0.268 Ohm/km
  • Specification core insulation: Crosslinked polyethylene (XLPE)
  • REACH Date: 2023-03-13
  • REACH Information obligation: No