AML is a halogen-free, TPI-insulated, PE-sheathed cable with annealed, low-strand aluminum conductors. AML contains materials with little climate impact and are easy to recycle.
- Article number: 0008890
- Suppl. article no: 15401598-201-00
- Ean no: 7330000182271
- Material class QA1410
Technical data
- Packagin Size: 1 M/500 M
- Cable type: AML
- Nominal cross section conductor: 240 mm²
- Number of cores: 4
- Dimension conductor x area: 4G240 mm²
- Outer diameter approximate: 54 mm
- Colour outer sheath: Black
- Weight: 3500 kg/km
- With protective conductor: Yes
- Conductor material: Aluminium
- Number of pilot/reduced conductors: 0
- Core identification: Colour
- Conductor category: Class 2 = stranded
- Nominal voltage U: 1 kV
- Nominal voltage U0: 0.6 kV
- Max. permitted conductor temperature: 90 °C
- Drain wire: No
- Screen: No
- Lead sheath: No
- Reaction-to-fire according to EN 13501-6: Class: None
- Reaction-to-fire according to EN 13501-6: Flaming droplets/particles: None
- Reaction-to-fire according to EN 13501-6: Smoke production: None
- Reaction-to-fire according to EN 13501-6: Acidity: None
- Fibre optic elements: No
- Halogen free according to EN IEC 60754-2: Yes
- Inner semi-conducting layer: No
- Concentric conductor: None
- Laminated sheath: No
- Conductive coating: No
- Shape of conductor: Sector-shaped
- Conductor surface: Bare
- Longitudinal water blocking conductors: No
- Material outer sheath: Other
- Permitted cable outer temperature after assembling without vibration: -40-70 °C
- Permitted cable outer temperature during assembling/handling: -20-50 °C
- Outer semi-conducting layer: No
- Min. permitted bending radius, stationary application/permanent installation: 432 mm
- Specification core insulation: Polypropylene (PP)
- Specification material outer sheath: Polyethylene (PE)
- Certified for shipboard application: No
- Certified as airport lighting cable: No
- Cable geometry: Round
- Conductor resistance at 20 °C: 0.125 Ohm/km
- Suitable for underground installation: Yes
- Max. tensile strength during installation: 28.8 kN
- With rodent protection: No
- UV resistant: Yes
- REACH Date: 2023-10-12
- GWP-tot (A1-A3): 12,2805 kgCO2e/M
- REACH Information obligation: No