AXQJ Easy ™ is a halogen-free, PEX-insulated and HFFR-sheathed cable with sector-shaped low-wire conductors made of aluminum. The cable has a shield of annealed copper wire with a counter-spiral. Easy to bend and scale
- Article number: 0008645
- Suppl. article no: 15163298-201-05
- Ean no: 7330000167919
- Material class QA1650
- This is an alternative to item 0014655
Technical data
- Packagin Size: 500 M
- Dimension conductor x area: 3x150/41 mm²
- Nominal cross section conductor: 150 mm²
- Number of cores: 3
- Outer diameter approx.: 40 mm
- Colour outer sheath: Black
- Nominal voltage U: 1 kV
- Screen: Yes
- Drain wire: No
- Concentric conductor: Copper
- Reaction-to-fire according to EN 13501-6: Class: Dca
- Permitted cable outer temperature after assembling without vibration: -40-70 °C
- Permitted cable outer temperature during assembling/handling: -10-40 °C
- Halogen free according to EN IEC 60754-2: Yes
- Shape of conductor: Sector-shaped
- Conductor category: Class 2 = stranded
- Conductor material: Aluminium
- Max. conductor temperature: 90 °C
- Material outer sheath: Polyolefin
- Nominal voltage U0: 0.6 kV
- Core identification: Colour
- Material core insulation: Other
- Reaction-to-fire according to EN 13501-6: Flaming droplets/particles: d2
- Laminated sheath: No
- Conductor surface: Bare
- Longitudinal water blocking screen: No
- Longitudinal water blocking conductors: No
- Min. permitted bending radius, stationary application/permanent installation: 320 mm
- Low smoke according to EN IEC 61034-2: Yes
- Reaction-to-fire according to EN 13501-6: Smoke production: s2
- Specification core insulation: Crosslinked polyethylene (XLPE)
- Reaction-to-fire according to EN 13501-6: Acidity: a2
- Nominal cross section concentric conductor: 41 mm²
- Weight: 2152 kg/km
- Certified for shipboard application: No
- Certified as airport lighting cable: No
- Cable geometry: Round
- Suitable for underground installation: Yes
- Suitable as installation cable: Yes
- Max. tensile strength during installation: 13.5 kN
- With protective conductor: Yes
- Core identification according to HD 308 S2: Yes
- Conductor resistance at 20 °C: 0.206 Ohm/km
- Oil resistant according to EN IEC 60811-404: Yes
- UV resistant: Yes
- GWP-tot (A1-A3): 13,6896 kgCO2e/M
- REACH Date: 2022-02-08
- REACH Information obligation: No