The cable is intended for permanent installation indoors and outdoors. MXQ Easy ™ steering is suitable for installation where both power and steering are needed, for example for charging vehicles where load steering is required.
- Article number: 0006580
- Suppl. article no: 14091998-201-00
- Ean no: 7330000162358
- Material class QA1210
Technical data
- Packagin Size: 1 M/500 M
- Cable type: MXQ Easy
- Number of cores: 5
- Nominal cross section conductor: 10 mm²
- Dimension conductor x area: 5G10+4x0.75 mm²
- Outer diameter approx.: 19.3 mm
- Colour outer sheath: Black
- Weight: 730 kg/km
- Nominal voltage U: 1 kV
- Nominal voltage U0: 0.6 kV
- Halogen free according to EN IEC 60754-2: Yes
- Reaction-to-fire according to EN 13501-6: Class: Dca
- Reaction-to-fire according to EN 13501-6: Smoke production: s2
- Reaction-to-fire according to EN 13501-6: Flaming droplets/particles: d2
- Reaction-to-fire according to EN 13501-6: Acidity: a2
- Conductor material: Copper
- Conductor category: Class 2 = stranded
- Shape of conductor: Round
- Number of pilot/reduced conductors: 4
- Screen: No
- Drain wire: Yes
- Lead sheath: No
- Permitted cable outer temperature after assembling without vibration: -40-70 °C
- Permitted cable outer temperature during assembling/handling: -10-50 °C
- Concentric conductor: None
- Material outer sheath: Polyolefin
- Core identification: Colour
- With protective conductor: Yes
- Material core insulation: Other
- Max. conductor temperature: 90 °C
- Fibre optic elements: No
- Inner semi-conducting layer: No
- Laminated sheath: No
- Conductive coating: No
- Conductor surface: Bare
- Longitudinal water blocking screen: No
- Longitudinal water blocking conductors: No
- Outer semi-conducting layer: No
- Certified for shipboard application: No
- Certified as airport lighting cable: No
- Cable geometry: Round
- Suitable as installation cable: Yes
- Min. permitted bending radius, stationary application/permanent installation: 160 mm
- Core identification according to HD 308 S2: Yes
- Conductor resistance at 20 °C: 1.83 Ohm/km
- Specification core insulation: Crosslinked polyethylene (XLPE)
- Armouring/reinforcement: None
- Circuit integrity: None
- Circuit integrity according to BS 6387 CWZ: No
- Circuit integrity according to BS 8434-2: No
- Circuit integrity according to BS 8491: No
- Suitable for underground installation: Yes
- Suitable as medium-voltage cable: No
- Max. tensile strength during installation: 2.5 kN
- Nominal cross section pilot/reduced conductors: 0.75 mm²
- Oil resistant according to EN IEC 60811-404: Yes
- Protective barrier: None
- UV resistant: Yes
- Suitable as high-voltage cable: No
- REACH Date: 2021-06-14
- REACH Information obligation: No
- Halogen free according to EN 60754-1/2: Yes
- Insulation integrity according to IEC 60331: No
- Insulation integrity: None