Feedback

Nexans

Medium voltage cable AXLJ-F TTCL 24 kV, Nexans

AXLJ-F TTCL 1X240/35 24KV (*6) K22)
Article number: 
0078240
Suppl. article no: 
21206098-201-00





 to see price and stock
The cable is longitudinally and transversely waterproof and intended for fixed installation outdoors in air, ground and water. The sheath has an outer semi-conductive layer. AXLJ-F TTCL is a longitudinally and transversely waterproof, halogen-free, PEX-insulated, copper-shielded 1-core cable with round aluminum conductor and PE sheath (LLD polyethylene). The cable is constructed according to SS 424 14 16. The conductor has a number of wires and resistance according to IEC 60228 class 2. Under the sheath is a full-coverage aluminum tape and the sheath consists of two layers. An inner UV-resistant white layer and an outer black semi-conductive layer. The sheath is marked with type/manufacturer/year+month/meter marking. AXLJF TTCL is not flame retardant. When crimping the cable's shield, the following applies: The actual copper area is one area step lower than the type marking and this means, for example, that a 25 mm² shield is spliced ​​with a 16 mm² splice tube. Lifemark(TM) recycling marking: Permanent marking on the outer sheath of the cable. The marking specifies the plastic qualities contained and prepares for future recycling of the cable. Standard: The cable is, where applicable, designed and tested in accordance with HD 620.5-K. The cable may be loaded in accordance with SS 424 14 16.
  • Article number: 
    0078240
  • Suppl. article no: 
    21206098-201-00
  • Ean no: 
    7330000132863
  • Material class 
    QA2400
Technical data
  • Cable type: AXLJ-F TTCL
  • Nominal cross section conductor: 240 mm²
  • Number of cores: 1
  • Dimension conductor x area: 1x240/35 mm²
  • Outer diameter approx.: 38 mm
  • Colour outer sheath: Black
  • Weight: 1628 kg/km
  • Conductor material: Aluminium
  • Core identification: None
  • Conductor category: Class 2 = stranded
  • Nominal voltage U: 24 kV
  • Nominal voltage U0: 14 kV
  • Max. permitted conductor temperature: 90 °C
  • Screen: Yes
  • Lead sheath: No
  • Reaction-to-fire according to EN 13501-6: Class: None
  • Reaction-to-fire according to EN 13501-6: Flaming droplets/particles: None
  • Reaction-to-fire according to EN 13501-6: Smoke production: None
  • Reaction-to-fire according to EN 13501-6: Acidity: None
  • Fibre optic elements: No
  • Halogen free according to EN IEC 60754-2: Yes
  • Inner semi-conducting layer: Yes
  • Concentric conductor: Copper
  • Laminated sheath: Yes
  • Conductive coating: Yes
  • Shape of conductor: Round
  • Conductor surface: Bare
  • Longitudinal water blocking screen: Yes
  • Longitudinal water blocking conductors: Yes
  • Material outer sheath: Other
  • Nominal cross section concentric conductor: 35 mm²
  • Permitted cable outer temperature after assembling without vibration: -40-70 °C
  • Permitted cable outer temperature during assembling/handling: -20-50 °C
  • Outer semi-conducting layer: Yes
  • Min. permitted bending radius, stationary application/permanent installation: 380 mm
  • Specification core insulation: Crosslinked polyethylene (XLPE)
  • Specification material outer sheath: Polyethylene (PE)
  • Cable geometry: Round
  • Conductor resistance at 20 °C: 0.125 Ohm/km
  • Core identification according to HD 308 S2: No
  • Radial water blocking cable: Yes
  • Suitable for underground installation: Yes
  • Max. tensile strength during installation: 7.2 kN
  • With rodent protection: No
  • Protective barrier: Al/PE
  • Suitable as medium-voltage cable: Yes
  • REACH Date: 2024-12-06
  • REACH Information obligation: No