Feedback

Medium voltage cable AXLJ-F TTCL 12 kV, Nexans - AXLJ-F TTCL 1X50/16 12KV (*0)                      K16)
Nexans

Medium voltage cable AXLJ-F TTCL 12 kV, Nexans

AXLJ-F TTCL 1X50/16 12KV (*0) K16)
Article number: 
0078110
Suppl. article no: 
21205098-201-00
Normally in stock
 to view the store status of the store
 to see price and stock
The cable is length- and crosswise waterproof and designed for fixed installation outdoors in air, ground and water. The sheath has an outer semi-conductor layer.
AXLJ-F TTCL is a length- and crosswise waterproof, halogen-free, PES-insulated, copper-shielded 1-wire cable with round aluminium wire and PE sheath (LLD polyethylene). The cable is designed in accordance with SS 424 14 16. The line has a wire count and resistance in accordance with IEC 60228 class 2. Under the sheath there is an all-covering aluminium band and the sheath consists of two layers. An inner UV-resistant white layer and an outer black semi-conductor layer. The jacket is marked type/manufacturer/year+month/metre marking. AXLJF TTCL is not fire-resistant.
When pressing the cable screen, the following shall apply: The actual copper area is one step longer than the type marking, which means that 25 mm² screen is spliced with 16 mm² sleeve.
Lifemark(TM) recycling marking: Resistant outer marking on the cable’s outer sheath. The marking specifies included plastic grades and preparation for future recycling of the cable.
Standard: The cable is, in applicable sections, designed and tested in accordance with HD 620.5-K. It is possible to apply load on the cable in accordance with SS 424 14 16.
  • Article number: 
    0078110
  • Suppl. article no: 
    21205098-201-00
  • Ean no: 
    7330000132665
  • Material class 
    QA2400
Technical data
  • Cable type: AXLJ-F TTCL
  • Nominal cross section conductor: 50 mm²
  • Number of cores: 1
  • Dimension conductor x area: 1x50/16 mm²
  • Outer diameter approximate: 23 mm
  • Colour outer sheath: Black
  • Weight: 530 kg/km
  • Weight/100 m: 55 kg
  • With protective conductor: Yes
  • Conductor material: Aluminium
  • Core identification: None
  • Conductor category: Class 2 = stranded
  • Nominal voltage U: 12 kV
  • Nominal voltage U0: 7 kV
  • Max. permitted conductor temperature: 90 °C
  • Screen: Yes
  • Lead sheath: No
  • Reaction-to-fire according to EN 13501-6: Class: None
  • Reaction-to-fire according to EN 13501-6: Flaming droplets/particles: None
  • Reaction-to-fire according to EN 13501-6: Smoke production: None
  • Reaction-to-fire according to EN 13501-6: Acidity: None
  • Fibre optic elements: No
  • Halogen free according to EN IEC 60754-2: Yes
  • Inner semi-conducting layer: Yes
  • Concentric conductor: Copper
  • Laminated sheath: Yes
  • Conductive coating: Yes
  • Shape of conductor: Round
  • Conductor surface: Bare
  • Longitudinal water blocking screen: Yes
  • Longitudinal water blocking conductors: Yes
  • Material outer sheath: Other
  • Nominal cross section concentric conductor: 16 mm²
  • Outer semi-conducting layer: Yes
  • Min. permitted bending radius, stationary application/permanent installation: 230 mm
  • Specification core insulation: Crosslinked polyethylene (XLPE)
  • Specification material outer sheath: Polyethylene (PE)
  • Cable geometry: Round
  • Conductor resistance at 20 °C: 0.641 Ohm/km
  • Circuit integrity: None
  • REACH Date: 2021-06-14
  • Armouring: No
  • REACH Information obligation: No
  • Halogen free according to EN 60754-1/2: Yes
  • Flame retardant: No
  • Insulation integrity according to IEC 60331: No
  • Oil resistant (according to IEC 60811-404): Yes
  • Insulation integrity: None